1. Full-load amps from kVA

Primary full-load current–
Secondary full-load current–

Three phase: I = kVA × 1000 ÷ (√3 × VLL). Single phase: I = kVA × 1000 ÷ V.

2. Size a transformer for a load

Measured or calculated maximum demand.
Self-cooled dry-type: 0.3% per 100 m above 1,000 m (IEEE C57.96).
e.g. a manufacturer’s high-ambient factor.
Load kVA–
With growth margin–
Combined derating factor–
Minimum nameplate kVA–
Next standard size–
Full-load current of that size–

Notes on using these results

  • Harmonic loads. Drives, rectifiers and IT equipment add heating that a growth margin does not cover reliably. Specify a K-factor or drive isolation rating instead of guessing a derate — see dry-type transformers.
  • Ambient temperature. Ratings normally assume a 40 °C maximum ambient. For hotter sites, use the manufacturer’s derating factor in “Other derating”.
  • Standard sizes shown are common ratings. Availability varies by manufacturer and voltage.
  • Conductor and overcurrent sizing follow the NEC and the actual installation; this tool does not size them.

For preliminary sizing only. Results are estimates from the inputs you enter; the final rating should be confirmed by a qualified engineer and the manufacturer.